Transmission voltage recovery delayed by stalled air conditioner compressors

TitleTransmission voltage recovery delayed by stalled air conditioner compressors
Publication TypeJournal Article
Year of Publication1992
AuthorsB.R. Williams, W.R. Schmus, D.C. Dawson
JournalIEEE Transactions on Power SystemsIEEE Transactions on Power Systems
Volume7
Issue3
Pagination1173-1181
Date Published08/1992
ISBN Number0885-8950
KeywordsFIDVR, FIDVR-001, RTINA
Abstract

Southern California Edison Company (SCE) has experienced delayed voltage recovery following fault clearing on the transmission system. The authors describe these occurrences and document the studies which successfully modeled the voltage recovery process. The studies showed how the stalling of single-phase air conditioner compressors following a power system fault was the root cause of delayed voltage recovery. Tests of air conditioner response to voltage dips are documented. The results of these tests are used to derive the mathematical load models used in voltage recovery studies

DOI10.1109/59.207331